Three Phase Capacitance Inductance Tester RLC

RLC METER - EPDG-H

RLC METER

General Information:
Automatic capacitance inductance tester is specially developed for problems existing in substation field measurement of capacitance value of capacitor, it solved the following problems:
(1) Field measurement capacitor needs dismantling cables, not only the big workload but also easy to damage the capacitor.
(2) Low capacitance meter output voltage causes the fault detection rate is low.
The instrument has characteristics of small measured workload, fast and simple, stable performance, high measurement accuracy, high fault detection, etc.
(3) Reactor inductance measurement.

Technical Specifications:

Capacitance: Measurable capacitance range: 0. 1μF ~ 3,300μF
Measurable capacity range: 5 20,000kvar
Measurement accuracy: ±(1.0% readings +0.02μF
Resolution: 0.001μF
Current: Current measurement range: 0 ~20A
Measurement accuracy: ±(3.0% readings +0.05A
Resolution: 0.01A
Inductance: Inductance measurement range:

Small inductance mode 0.1mH~5mH

Large inductance mode 5 mH~50H

Inductive reactance measurement range: 50mΩ~20KΩ
Measurement accuracy: ±(3.0% readings +0.05mH)
Resolution: 0.01mH
Resistance measurement: Resistance measurement range:

Small resistance mode 50mΩ~1Ω

Large resistance mode 1Ω~20KΩ

Measurement accuracy: ±(3.0% readings +0.05Ω)
Resolution: 0.01 Ω
Power supply: Rated voltage: power frequency 220V±10%
Rated frequency: 50Hz
Rated output: 2V/20V/500VA
Working condition: Environmental temperature:

-10℃ ~ +50℃

Relative humidity: ≤90%
Weight: 370×260×220 mm / 15 kg